Alarms and remote monitoring
Power-failure alarms that still work when power is out
Updated
A power-failure alarm has to run on the one thing it is watching for the loss of. It needs four parts: a battery that keeps the whole alarm path alive (sensor input, controller, modem), a reliable way to sense that mains power is gone, a communication path that does not depend on site power, and a remote service that raises an alarm when the site goes silent. Miss any one, and the alarm fails exactly when it is needed.
Why power loss is the alarm that matters most
For water-dependent sites, a power cut stops pumps, blowers and oxygen generators all at once. The Southern Regional Aquaculture Center’s example: after a power failure in a warmwater recirculating system at 84 °F, oxygen falls to a stressful 3 ppm in 16 minutes, or in under 6 minutes at higher density (SRAC 452). SRAC calls automatic phone alarms “essential in alerting key personnel to power failures”, and recommends an automatic transfer switch so the generator starts when nobody is present.
The alarm does not replace those automatic backups. It tells someone that they ran, or that they did not.
Sizing the battery for the alarm path
List every device the alarm needs to get a message out, not just the alarm box:
- the sensor or input that detects mains loss
- the controller or dialer
- the modem or router (cellular modem, or the network terminal for a wired line)
- any network switch between them
- a local horn or strobe, if it must sound during the outage
Then calculate runtime:
usable energy (Wh) = battery voltage (V) x capacity (Ah) x usable fraction x conversion efficiency
runtime (h) = usable energy (Wh) / average load (W)
A worked example with assumed figures, not a product specification:
battery: 12 V, 7 Ah sealed lead-acid = 84 Wh nominal
usable: 50% depth of discharge (for battery life) = 42 Wh
convert: 85% efficient DC-DC converter = 35.7 Wh
load: controller 6 W + cellular modem 3 W avg = 9 W
runtime: 35.7 Wh / 9 W = about 4 hours
Then derate. Battery capacity falls with age and in cold enclosures, so size for the battery near the end of its life, not when new. Measure the real load with a meter, including the modem’s peaks while it transmits. And decide how long the alarm must last: through the longest outage you have seen, plus the time for someone to arrive with a generator or a replacement battery. The Freshwater Institute has lived through a week-long outage (Hatchery International).
For comparison, here are the battery runtimes some commercial alarm units list, as of 19 November 2026:
| Unit | Communication | Listed battery backup |
|---|---|---|
| Sensaphone 400 and 800 | Landline voice | 24 hours, on 6 C-cell batteries (Sensaphone) |
| RACO Verbatim | Landline or wireless telephone | 20 hours (RACO) |
| Sensaphone Sentry | LTE-M cellular | 12 hours, rechargeable (Sensaphone) |
| Sensaphone Sentinel (cellular) | 4G LTE cellular | 8 hours for unit and modem (Sensaphone) |
A dedicated battery for the alarm path is better than putting the alarm on the same UPS as a PC or server: a large UPS shared with other loads empties faster than its rating suggests, and when it runs down everything goes at once.
Detecting that mains power is gone
The alarm must sense mains loss while running on battery itself. Common methods:
- AC-sense input on the alarm unit. Many dialers watch their own plug-in supply; Sensaphone’s 400 and 800 power supply “also monitors for power failures” (Sensaphone), and the RACO Verbatim monitors internal AC power (RACO).
- A relay powered by the circuit you care about. A relay coil on the pump circuit, with its contact wired to a digital input, opens when that circuit dies. This catches a tripped breaker on the pump circuit even when the alarm’s own outlet is still live.
- A UPS or DC power supply status signal. Many UPS units and DIN-rail supplies give a dry contact or a data signal for “on battery” or “AC fail”.
- A phase monitor relay on three-phase equipment. Loss of one phase can stop or damage a motor while lighting circuits stay on.
Sense power where the loss would hurt. An alarm plugged into an outlet on a different circuit from the pumps can report “power OK” while the pumps are dead.
Also alarm on:
- Power restored, so the on-call person knows whether to keep driving.
- Generator running but transfer failed, by sensing the load side of the transfer switch.
- Alarm battery low, so the last message goes out before the unit dies.
Cellular or landline during an outage?
Each path has its own dependence on power somewhere else.
Copper landline. A traditional copper line is powered from the telephone exchange, so it can keep working when site power is gone. Many lines sold as “landline” are now voice over fiber, cable or the internet, which needs a powered terminal or modem at the site. Ask your provider how your line is delivered, and if it needs local power, put that terminal on the alarm battery. Copper service is also being retired: AT&T plans to retire the large majority of its copper outside California by the end of 2029, and in January 2026 had federal approval to start on more than 30 percent of that footprint (Broadband Breakfast). Check your line’s future before relying on it.
Cellular. The site’s modem runs on your battery, and the network side depends on the tower’s backup power, which you do not control. Use a current network technology: AT&T, T-Mobile and Verizon scheduled their 3G shutdowns for February, July and December 2022 respectively (NBC New York), and alarm units that depended on 3G stopped calling. Check signal strength at the actual mounting position, inside the enclosure.
Both. The Freshwater Institute added an analog backup phone line after its one significant fish loss, which was traced to an alarm failure (Hatchery International). Two independent paths, each on battery, is the robust answer for a site where an hour of downtime means lost stock.
The alarm that needs no site power: silence detection
If the whole site goes dark, including its battery, it cannot send anything. A cloud or remote service closes that gap by expecting a regular heartbeat from each site and alarming when it stops. That alarm is generated outside the site, so it works even if the site’s equipment is destroyed. Set the heartbeat interval from how fast your process fails: a few minutes for a dense fish system, longer for a slow tank.
A heartbeat alarm cannot tell you why the site went quiet. Treat it as “power or communication lost, go and look”.
Testing a power-failure alarm
Test by cutting power, not by pressing a test button:
- On a quiet afternoon, switch off the breaker that feeds the equipment.
- Time when the alarm reached someone, and who acknowledged it.
- Confirm the generator started and transferred, and that backup oxygen opened if fitted.
- Leave the alarm on battery for an hour and log the battery voltage, to check the runtime estimate.
- Restore power and confirm the “power restored” message.
The Freshwater Institute tests generator start and power transfer weekly (Hatchery International), and Ebeling recommends regular tests of automatic backups and the phone dialer, including some unannounced ones (Global Seafood Alliance). Replace sealed batteries on a schedule rather than waiting for a failed test.
Where halfnine fits
halfnine plans a controller and cloud alarm service. Its power input, battery options, power-loss sensing and heartbeat interval are not yet specified: To be decided: power and backup design, cellular and wired options, heartbeat interval. The sizing method and tests above apply to any system.
Sources
- SRAC Publication No. 452, Recirculating Aquaculture Tank Production Systems: Management of Recirculating Systems (Masser, Rakocy, Losordo, March 1999 revision), accessed 2026-11-19
- Emergency response for RAS, Hatchery International (John Davidson, 25 April 2022), accessed 2026-11-19
- Process control, monitoring options in intensive recirculation systems, Global Seafood Alliance (James M. Ebeling, 1 June 2003), accessed 2026-11-19
- Sensaphone 400 and 800 Monitoring Systems product page, accessed 2026-11-19
- Sensaphone Sentinel Monitoring System with Cellular Modem product page, accessed 2026-11-19
- Sensaphone Sentry Monitoring System product page, accessed 2026-11-19
- RACO Verbatim Autodialer product page, accessed 2026-11-19
- 3G Networks Will Shut Down in 2022. Why You May Need to Upgrade Soon, NBC New York, accessed 2026-11-19
- AT&T Approved to Discontinue Service at More Than 30% of Copper Footprint This Year, Broadband Breakfast (13 January 2026), accessed 2026-11-19