Standards and compliance
The UL 508 to UL 61010-2-201 transition
Updated
On 2026-10-28, the last UL 508 certifications for programmable controllers were withdrawn. UL 508’s 19th edition removed programmable controllers from its scope and points them to UL 61010-2-201, used with UL 61010-1. Controllers already in service keep working and are not recalled; the change affects what manufacturers can sell under a valid certification and what panel builders can specify from now on.
This page explains the standards; it is not legal or certification advice.
What are the dates?
| Date | What happened | Source |
|---|---|---|
| February 2013 | IEC publishes IEC 61010-2-201 | UL white paper |
| January 2014 | UL publishes UL 61010-2-201 | same |
| 2016-04-01 | UL stops accepting new PLC submittals to UL 508 or UL 61131-2; EN 61131-2 withdrawn as the EU’s presumption-of-conformity standard for PLCs | same |
| 2016-07-25 | Intertek: all new programmable controller investigations must use UL 61010-1 and UL 61010-2-201; unchanged UL 508 certifications may stay | Intertek 2016 notice |
| 2025-04-04 | Intertek issues notice for UL 508 19th edition | Intertek 2025 notice |
| 2026-05-11 | Intertek issues notice for UL 61010-2-201 3rd edition (2026) | Intertek 2026 notice |
| 2026-10-28 | Effective date: programmable controllers must be certified to UL 61010-2-201; other UL 508 products to UL 508 Ed. 19; reports not updated are withdrawn | Intertek 2025 notice |
| 2028-02-06 | Effective date for UL 61010-2-201 Ed. 3 | Intertek 2026 notice |
So the transition happened in two steps. From 2016, new controller designs went to UL 61010-2-201, but existing UL 508 certifications were grandfathered as long as the construction did not change. On 2026-10-28 the grandfathering ended.
What exactly changed on 2026-10-28?
The Intertek notice gives two rules:
- “All programmable controllers currently certified to UL 508 must be certified to UL 61010-2-201 prior to the effective date.”
- “All products currently certified to UL 508 that are not programmable controllers must be certified to the 19th edition of UL 508 prior to the effective date.”
UL 508 Ed. 19 (2024) adds clause 1.12, which states that programmable controllers are covered by UL 61010-2-201. The same edition also adds a marking table for overload relay trip classes (Class 10, 20, 30 at 600 % of current element rating) and new service-equipment barrier requirements. Those changes matter for contactors, overload relays and service equipment, not for controllers.
Intertek’s notice says reports not updated by the effective date “will be withdrawn”. It was issued by Intertek (ETL); the date matches across certification bodies because it follows the UL 508 standard, but check with your own body if your certificates are from UL Solutions, CSA or TÜV.
What changes technically for a controller?
UL 61010-2-201 is not a renamed UL 508. According to UL’s white paper, the main differences are:
| Topic | UL 508 | UL 61010-2-201 (with UL 61010-1) |
|---|---|---|
| Protection from hazardous parts | One level | Two levels |
| Single-fault testing | No named components | Named components tested under single fault |
| Mechanical hazards | Construction rules, references | Evaluation of sharp edges, moving parts, stability; risk assessment in some cases |
| Fire enclosure material | Varies | At least V-1 |
| Production line tests | Fewer | Protective earth, voltage test, floating circuits |
| Creepage, clearance, load classification | North American approach | IEC approach |
A controller that passed UL 508 years ago may need design changes, not just paperwork, to pass UL 61010-2-201.
What does this mean for buyers?
- Installed equipment is not affected. The transition is about certification of products being made and sold. Your running controllers do not lose their safety because a report was withdrawn.
- New purchases should carry UL 61010-2-201. Ask for the UL file number and check it in UL Product iQ. If a vendor still quotes a UL 508 certificate for a programmable controller, ask whether it has been updated or withdrawn.
- Spares and replacements. If a discontinued controller was never moved to UL 61010-2-201, new stock may no longer be shipped under its mark. Plan replacements and check what your inspector accepts for like-for-like swaps.
- Look ahead to 2028-02-06. The 3rd edition of UL 61010-2-201 takes effect then. A product certified today to the 2nd edition will need its report updated by that date (Intertek).
What does this mean for panel builders?
UL 508A panels can contain listed or recognized programmable controllers. UL’s component requirements document already names the standards for category NRAQ (listed) and NRAQ2 (recognized) programmable controllers as “UL 508 or UL 61010-1 and UL 61010-2-201”. After 2026-10-28, only the second route remains for products still in production.
Practical steps:
- Audit your bill of materials for controllers, I/O and HMIs whose certificates cite UL 508.
- Confirm each has moved to UL 61010-2-201, or find a replacement.
- Update your UL 508A procedure if it names specific models.
- Keep the evidence (certificate, Product iQ printout) with the panel file for the inspector.
Other UL 508 devices in your panels (contactors, relays, overloads) are not leaving UL 508; they move to its 19th edition, so their certificates should now cite UL 508 Ed. 19.
What about Canada and the EU?
The EU moved first: EN 61131-2 stopped giving presumption of conformity for PLCs on 2016-04-01, and EN 61010-1 with EN 61010-2-201 took over (UL white paper). In Canada, CAN/CSA-C22.2 No. 61010-2-201 exists, but as of the 2015 white paper Canada had not set a transition date from CSA C22.2 No. 142. To be decided: current Canadian transition status, confirmed with CSA or a Canadian certification body.
Where does halfnine stand?
halfnine has no product yet and no certification. Any controller it ships into North American industrial markets would be evaluated to UL 61010-2-201 from the start, so the UL 508 transition does not apply to it directly. To be decided: certification plan and edition targeted, given the 2028-02-06 date for Ed. 3.
Sources
- Intertek Standards Update Notice: UL 508 (issued 2025-04-04, effective 2026-10-28), accessed 2026-11-19
- Intertek SUN: Transition of programmable controller from UL 508 to UL 61010-1 and UL 61010-2-201 (2016), accessed 2026-11-19
- UL white paper: Programmable Logic Controllers and IEC 61010-2-201 (2015), accessed 2026-11-19
- Intertek Standards Update Notice: UL 61010-2-201:2026 Ed. 3 (issued 2026-05-11, effective 2028-02-06), accessed 2026-11-19
- UL: Requirements for Components Used in Industrial Control Panels (2020-04-13), accessed 2026-11-19