Standards and compliance
UL 61010-2-201 for programmable controllers
Updated
UL 61010-2-201 is the safety standard that programmable controllers, remote I/O, HMIs and similar control equipment are certified to in the United States. It is a “particular” standard: it only works together with the general standard UL 61010-1, and it is a direct adoption of IEC 61010-2-201 with no US national deviations. Since 2026-10-28, a programmable controller can no longer hold a UL 508 certification; it needs UL 61010-2-201.
This page explains the standards; it is not legal or certification advice. Your certification body and the local authority having jurisdiction (AHJ) have the final word.
What does UL 61010-2-201 cover?
The IEC original lists the kinds of equipment it applies to. As summarised in UL’s white paper on the standard, that includes:
- programmable controllers (PLCs and programmable automation controllers, PACs)
- components of distributed control systems (DCS)
- components of remote I/O systems
- industrial computers, and programming and debugging tools
- human-machine interfaces (HMIs)
- stand-alone power supplies
- any other product that performs the function of control equipment or its peripherals
It is an electrical safety standard. The same white paper notes that it does not address reliability, functionality or performance, mechanical and environmental requirements for operation and transport (still covered by the IEC 61131 series), functional safety, EMC, or equipment for explosive atmospheres. A controller can therefore be UL 61010-2-201 certified and still fail in the field for reasons the standard never tested.
How does it relate to UL 61010-1 and IEC 61010-2-201?
| Standard | Role | Region |
|---|---|---|
| IEC 61010-1 | General safety requirements for measurement, control and laboratory equipment | International |
| IEC 61010-2-201 | Particular requirements for control equipment; amends and adds to 61010-1 | International |
| UL 61010-1 / UL 61010-2-201 | US adoptions of the above | United States |
| CAN/CSA-C22.2 No. 61010-1 / No. 61010-2-201 | Canadian adoptions | Canada |
| EN 61010-1 / EN 61010-2-201 | European adoptions, used for CE marking under the Low Voltage Directive | EU |
A certification always cites both parts. Intertek’s UL 508 notice puts it plainly: “UL 61010-2-201 is to be used in conjunction with UL 61010-1.” UL Solutions’ PLC certification page lists the deliverables per market: a US/Canada mark to UL/CSA 61010-1 and 61010-2-201, a CB report to IEC 61010-1 and 61010-2-201, and documentation for CE marking to EN 61010-1 and EN 61010-2-201.
UL published UL 61010-2-201 in January 2014 and CSA published its version in April 2014, and both were adopted from the IEC text with no national deviations. That is why one test programme under the IECEE CB Scheme can support the US, Canadian and European certifications together, which Intertek explicitly recommends for controllers moving off UL 508.
Which edition applies now?
Editions move, and certificates name a specific one.
- UL 61010-2-201:2018 (2nd edition, revised 2022-08-08) is the edition most current certificates cite. Arduino’s Opta controllers, for example, were certified on 2022-11-07 to UL 61010-2-201 and CSA C22.2 No. 61010-2-201:18, 2nd edition.
- UL 61010-2-201:2026 (3rd edition) is published. Intertek’s notice issued 2026-05-11 sets an effective date of 2028-02-06, after which reports not updated to the 3rd edition are withdrawn.
The 3rd edition changes, per that notice, include: a clarified scope for related equipment; a rule that control equipment providing safety functions to protect people must be used with a functional safety standard (for example IEC 61508-1, ISO 13849-1, UL 991 and UL 1998, or UL 62745); new subclauses on insulation and wiring for SELV/PELV circuits; added requirements for glass displays; and removal of the drop test and of the requirements on fluid and solid foreign objects.
A product designed in 2026–2027 should be designed against the 3rd edition, or it faces a re-evaluation within about a year of certification.
What does the standard actually test?
UL’s white paper lists the requirements that differed most from UL 508 and IEC 61131-2 when the standard arrived:
- Two levels of protection between accessible parts and hazardous parts. UL 508 required one.
- Mechanical hazards, including sharp edges, moving parts and instability, with a risk assessment in some cases.
- Single-fault testing of named components such as capacitors, mains transformers and interlocks.
- Enclosures and materials: fire enclosures need at least a V-1 flame rating, and panel-mounted controllers that form part of an enclosure may need UL 50E environmental ratings.
- Production line tests: protective earth, voltage tests and, where relevant, a floating-circuit test.
- Marking durability against cleaning agents and isopropyl alcohol.
Who needs it?
Controller manufacturers selling into North American industrial markets. If a product is sold as a programmable controller, I/O module or HMI for industrial control, UL 61010-2-201 (with UL 61010-1) is the standard an NRTL will certify it to. Since 2026-10-28, UL 508 is no longer an option for programmable controllers (Intertek).
Panel builders and integrators, indirectly. UL’s component requirements for UL 508A panels accept listed programmable controllers (UL category NRAQ) and recognized ones (NRAQ2) certified to “UL 508 or UL 61010-1 and UL 61010-2-201”. A certified controller is the simplest path into a listed panel. See UL 508A panels and the controllers inside them.
End users and specifiers, when a site, insurer or inspector requires listed equipment. Ask for the certificate or the UL Product iQ entry, not a datasheet logo. Arduino’s certificate itself notes that a Certificate of Compliance “does not provide authorization to apply the UL Mark”; only products bearing the mark under follow-up service are certified.
Who does not: hobby and lab use, and products sold only outside North America (though EN 61010-2-201 serves the same role for CE marking).
How do you check a controller’s certification?
- Find the UL file number (for example E531326) on the label or the manufacturer’s certificate.
- Look it up in UL Product iQ, linked from the certificate, and confirm the model numbers and the category: NRAQ means listed, NRAQ2 means recognized.
- Check which edition of UL 61010-2-201 the report cites, and whether the manufacturer has a plan for the 3rd edition before 2028-02-06.
- For Canada, confirm the “c” in cULus or a CSA mark; for the EU, ask for the CB certificate or the EU Declaration of Conformity citing EN 61010-2-201.
What about halfnine?
halfnine’s controller does not exist yet, so it holds no certification. To be decided: certification plan, target standard edition, test lab and expected date. Until that exists, treat any Pi-based controller without a UL file number as an unlisted product.
Sources
- UL white paper: Programmable Logic Controllers and IEC 61010-2-201 (2015), accessed 2026-11-19
- Intertek Standards Update Notice: UL 508 (issued 2025-04-04, effective 2026-10-28), accessed 2026-11-19
- Intertek Standards Update Notice: UL 61010-2-201:2026 Ed. 3 (issued 2026-05-11, effective 2028-02-06), accessed 2026-11-19
- UL Solutions, PLC unit testing and certification, accessed 2026-11-19
- UL Certificate of Compliance E531326, Arduino Opta programmable controllers (2022-11-07), accessed 2026-11-19
- UL: Requirements for Components Used in Industrial Control Panels (2020-04-13), accessed 2026-11-19